Voltage
600V or less
Construction
RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP).
Copper conductor is also available.
Standard
RHH or RHW-2 or USE-2 conductors meet or exceed UL Standard 44 (for RHH or RHW-2), UL Standard 854(for USE-2), Federal Specification A-A-59544, and requirements of the NEC. Or other standards required by customers.
Features
1.-40℃----90℃
2.Abrasion, high-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1. RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the NEC.
2. May also be used as underground service entrance cable, for direct burial, at conductor temperatures not to exceed 90℃.
3. When used as RHH, conductor temperatures shall not exceed 90℃ in dry locations.
4. When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90℃ in wet or dry locations.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V or less
Construction
Sino-cables SE Type is constructed with sunlight resistant resistant Type XHHW-2 conductors. Aluminum conductors are AA-8000 series Aluminum Alloy, Compact stranded.
SE Style R Cable assembly plus reinforcement tape are jacketed with gray sunlight resistant polyvinyl chloride(PVC). Available as 2 conductor ( 2 insulated phase conductors, bare ground), 3 conductor(2 insulated phase conductors, insulated neutral, bare equipment ground), or 4 conductor(3 insulated phase conductors, insulated neutral, bare equipment ground) .
SE Style U Cable assembly plus an overall concentrically applied neutral and reinforcement tape are jacketed with gray sunlight resistant polyvinyl chloride (PVC).
Copper conductor is also available.
Standard
UL 44, UL 854, Federal Specification A-A-59544, and requirements of the NEC.
Features
1.-40℃----90℃
2.Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.SE, service entrance cable is used to convey power from service drop to the meter base and from the meter base to the distribution panelboard; however, it may be used in all applications where Type SE cable is permitted
2.may be used in wet or dry locations at temperatures not to exceed 90℃.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V or less
Construction
Sino-cables XHHW-2 type aluminum conductors are annealed AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture and high-heat resistant black cross-linked polyethylene. Conductor sizes AWG 2 and larger listed and marked sunlight resistant in black only.
Copper conductor is also available.
Standard
XHHW-2 conductors meet or exceed UL Standard 44 .Federal Specification A-A-59544, and requirements of the NEC Type XHHW-2 meets and exceeds all construction requirements of ICEA S-95-658(NEMA WC 70)-Non shielded 0-2kv Cables, with testing frequencies based on UL requirements.
Features
1.-40℃----90℃
2.High-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.XHHW-2 conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electric Code(NEC).
2.May also be used in wet or dry locations at temperatures not to exceed 90℃.
3.Voltage rating for RW90 cable is 600V.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V or less
Construction
Sino-cables MC Type is constructed with Type XHHW-2 conductors rated 90℃ wet or dry, and a bare equipment grounding conductor. The Conductors are AA-8000 series Aluminum Alloy compact stranded. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Individual conductors are color coded per ICEA S-58-679, Method 3, Table 2 (Single color compounds with surface printing). A PVC outer sheath is needed for direct burial.
Copper conductor is also available.
Standard
UL 44, UL 1569 for type MC; ICEA S – 95-658; NEMA WC70; Federal Spec A-A59544 (formerly J–C–30B); IEEEE 1202 70,000 BTU vertical flame test; CSA Spec. C22.2, No. 51 - Armoured Cables.
Features
1. Up to 50% fewer installation steps; Pre-assembled and pre-tested; Lighter weight; Flexible, unlimited bends; Lower material and labor costs(Reduces installation costs up to 50% over pipe and wire); Ideal for vertical applications.
2. Cable reverse wound on reel for ease of pulling and installation When pulling from coils, pull from inside to ensure of installation.
3. Anti-short bushings are not required for use with MC cable per the NEC and UL.
Applications
1. Sino-cables MC Type is suitable for use in branch, feeder and service power distribution under high ambient temperature in commercial, industrial, institutional, casinos and multi-residential buildings; for power, lighting, control and signal circuits; in concealed or exposed installations; Fished or embedded in plaster; in environmental air-handling spaces per NEC 300.22; in places of assembly per NEC 518.4 and theaters per NEC 520.5; in aerial applications when attached to a messenger; for installation in cable tray and approved raceways; under raised floors for IT equipment per NEC 645.5(D) and 645.5(D)(2); Class I Div 2, Class II Div 2, Class III Div 1 hazardous locations.
2. used in wet or dry locations at temperatures not to exceed 90°C.
3. Available with PVC jacket for direct burial and encasement in concrete.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V or less
Construction
Sino-cables MHF type consists of four quadruplexed type RHH or RHW-2 or USE-2 with AA-8000 series, Aluminum Alloy compacted conductors and cross-linked polyethylene (XLP) insulation. The conductors are cabled together with a green XLP insulted aluminum ground. The grounded (neutral) conductor is identified by a longitudinal white stripe to eliminate the need for field marking per the NEC.
Standard
UL 44, UL 854, Federal Specification A-A-59544, requirements of the NEC, and other standards required by customers.
Features
1.-40℃----90℃
2.High-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1. Sino-cables type Mobile Home Feeder(MHF) is intended for the connection of mobile homes to a supply of electricity where permanent wiring is required as specified in the NEC in raceways and underground installations.
2. Suitable for direct burial in earth at conductor temperatures not to exceed 90℃ in wet or dry locations.
3. Three sizes available (with and without reduced neutral):100,150, and 200 ampere ratings..
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V or less
Construction
Sino-cables RW90 type aluminum conductors are annealed AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture and high-heat resistant, low temperature black XLPE(cross-linked polyethylene). Standard black sizes 6 and larger is sunlight resistant and is marked "Sun Res".
Copper conductor is also available.
Standard
CSA Spec. C22.2, No. 38.
Features
1.-40℃----90℃
2.High-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by customers.
Applications
RW90 is for open wiring and used in raceways (except cabletroughs and ventilated flexible cableways) in dry or wet locations. For open wiring exposed to the weather. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C. Approved for use on ceiling fixtures.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
2KV
Construction
Sino cables type PV wire 2kv is AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat, and sunlight resistant cross-linked polyethylene (XLP).
Copper conductor is also available.
Standard
UL4703; UL44; UL854; CSA C22.2 NO. 271; NEC Article 690, or other standards required by customers.
Features
1.-40℃----90℃, RoHs compliant.
2.High-Heat, Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.Sino cables type PV wire is primarily used for interconnection wiring of grounded and ungrounded photovoltaic power systems which do not exceed 2000 volt. solar power applications per NEC Article 690.
2.Rated 90℃ for exposed or concealed wiring in wet or dry locations.
3.Rated for direct burial conduit.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
1KV
Construction
Sino cables type RWU90 1kv is AA-8000 series Aluminum Alloy, compact stranded. Insulation is abrasion, moisture, heat, and sunlight resistant, low temperature and fire retardant cross-linked polyethylene (XLP).
Copper conductor is also available.
Standard
CSA Spec. C22.2, No. 38-05, or other standards required by customers.
Features
1.-40℃----90℃, RoHs compliant.
2.Abrasion, high-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.Sino cables type RWU90 1kv is for use For use above or below ground in solar applications.
2.direct burial.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
2KV
Construction
Sino cables type RHH/RHW-2 2kv is AA-8000 series Aluminum Alloy, compact stranded. Insulation is abrasion, moisture, heat, and sunlight resistant and fire retardant cross-linked polyethylene (XLP).
Copper conductor is also available.
Standard
UL44; NEC article 690; ICEA S-95-685/NEMA WC70, or other standards required by customers.
Features
1.-40℃----90℃, RoHs compliant.
2.Abrasion, high-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.Sino cables type RHH/RHW-2 2KV is for use from the lower control box at the base of the wind power tower and out to the step-up transformer through conduit.
2.For use in free air, raceways or direct burial in accordance with NEC.
3.Industrial environments where superior insulation toughness and chemical resistance is required.
4.Maximum operating temperature not to exceed 90℃in wet or dry locations.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
2KV
Construction
Sino cables type DLO Cables are manufactured in sizes 6 AWG through 1111.1 kcmil with stranded tinned annealed copper. A paper or polyester tape separates the conductor from the EPDM rubber insulation to aid in stripping. A black, heavy duty CPE sunlight resistant jacket is extruded over the insulation.
Standard
UL44, or other standards required by customers.
Features
1.Max permissible continuous operating temperature of conductor shall not exceed 90℃.
2.oils, acids, alkalines, heat, flame, sunlight, and abrasion resistant.
3.RoHs compliant.
4.bending radius is only 5 times of the outer dia. of cable.
Applications
1.DLO is utilized within the turbine and tower, as well as from the tower to the transformer in wind applications.
2.Suitable for use in wet or dry areas, conduits, ducts, troughs or trays, and where superior electrical properties are desired.
3.Maximum continuous conductor temperature for normal operation is 90°C in dry locations and 75°C for wet.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
Voltage
600V
Construction
Sino cables type SOOW is manufactured with bare flexible copper conductor insulated by ethylene-propylene rubber (EPR). Two, three, four or five insulated conductors are cabled together with filler and sheathed with chlorinated polyethylene.
Standard
Features
1.Max permissible continuous operating temperature of conductor shall not exceed 90℃.
2.oils, acids, alkalines, heat, flame, sunlight, and abrasion resistant
3.bending radius is only 5 times of the outer dia. of cable.
4.RoHs compliant.
Applications
SOOW for Wind Turbine is used for potable tools, equipment, appliances, small motors and associated machinery in the wind turbine. It is also used for industry equipment, heavy tools, battery chargers, portable lights and power extensions.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded
Aluminum Alloy UL CSA Standard
Description
Voltage
600V or less
Construction
RHH or RHW-2 or USE-2 aluminum conductors are AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linked polyethylene (XLP).
Copper conductor is also available.
Standard
RHH or RHW-2 or USE-2 conductors meet or exceed UL Standard 44 (for RHH or RHW-2), UL Standard 854(for USE-2), Federal Specification A-A-59544, and requirements of the NEC. Or other standards required by customers.
Features
℃----90℃
, high-Heat and Moisture and Sunlight Resistant.
or higher required by UL.
Applications
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
WEIGHTS AND MEASUREMENTS |
||||||
CONDUCTOR |
INSULATION |
NOMINAL |
AMPACITIES*(AMPS) |
APPROX |
||
60℃ |
75℃ |
90℃ |
||||
8 |
60 |
258 |
30 |
40 |
45 |
36 |
6 |
60 |
293 |
40 |
50 |
60 |
49 |
4 |
60 |
337 |
55 |
65 |
75 |
65 |
2 |
60 |
392 |
75 |
90 |
100 |
94 |
1 |
80 |
463 |
85 |
100 |
115 |
126 |
1/0 |
80 |
500 |
100 |
120 |
135 |
151 |
2/0 |
80 |
540 |
115 |
135 |
150 |
182 |
3/0 |
80 |
587 |
130 |
155 |
175 |
221 |
4/0 |
80 |
639 |
150 |
180 |
205 |
269 |
250 |
95 |
714 |
170 |
205 |
230 |
326 |
300 |
95 |
764 |
190 |
230 |
255 |
381 |
350 |
95 |
810 |
210 |
250 |
280 |
435 |
400 |
95 |
853 |
225 |
270 |
305 |
488 |
500 |
95 |
930 |
260 |
310 |
350 |
595 |
700 |
110 |
1101 |
310 |
375 |
420 |
829 |
750 |
110 |
1132 |
320 |
385 |
435 |
881 |
1000 |
110 |
1284 |
375 |
445 |
500 |
1145 |
* Ampacities based on CEC Part 1, Table 4 for not more than three conductors in raceway. For underground installations, refer to CEC, Rule 4-004 for Ampacity rating. *All values are nominal and subject to correction |
600V Cable XHHW-2 type aluminum conductors
Aluminum Alloy UL CSA Standard
Description
Voltage
600V or less
Construction
Sino-cables XHHW-2 type aluminum conductors are annealed AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture and high-heat resistant black cross-linked polyethylene. Conductor sizes AWG 2 and larger listed and marked sunlight resistant in black only.
Copper conductor is also available.
Standard
XHHW-2 conductors meet or exceed UL Standard 44 .Federal Specification A-A-59544, and requirements of the NEC Type XHHW-2 meets and exceeds all construction requirements of ICEA S-95-658(NEMA WC 70)-Non shielded 0-2kv Cables, with testing frequencies based on UL requirements.
Features
℃----90℃
and Moisture and Sunlight Resistant.
or higher required by UL.
Applications
conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electric Code(NEC).
also be used in wet or dry locations at temperatures not to exceed 90℃.
rating for RW90 cable is 600V.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
W E I G H T S. M E A S U R E M E N T S |
||||||
CONDUCTOR SIZE |
INSULATION |
NOMINAL . |
ALLOWABLE |
APPROXIMATE |
||
60℃ |
75℃ |
90℃ |
|
|||
8 |
45 |
228 |
30 |
40 |
45 |
31 |
6 |
45 |
263 |
40 |
50 |
60 |
43 |
4 |
45 |
307 |
55 |
65 |
75 |
67 |
2 |
45 |
362 |
75 |
90 |
100 |
87 |
1 |
55 |
413 |
85 |
100 |
115 |
109 |
1/0 |
55 |
450 |
100 |
120 |
135 |
133 |
2/0 |
55 |
490 |
115 |
135 |
150 |
162 |
3/0 |
55 |
537 |
130 |
155 |
175 |
201 |
4/0 |
55 |
589 |
150 |
180 |
205 |
246 |
250 |
65 |
654 |
170 |
205 |
230 |
297 |
300 |
65 |
704 |
190 |
230 |
255 |
352 |
350 |
65 |
750 |
210 |
250 |
280 |
402 |
400 |
65 |
793 |
225 |
270 |
305 |
454 |
500 |
65 |
870 |
260 |
310 |
350 |
555 |
600 |
80 |
980 |
285 |
340 |
385 |
680 |
700 |
80 |
1041 |
310 |
375 |
420 |
783 |
750 |
80 |
1072 |
320 |
385 |
435 |
832 |
1000 |
80 |
1224 |
375 |
445 |
500 |
1091 |
* Ampacities for not more than three conductors in raceway, based on ambient temperature of 30°C per Table 310-16 of the 2005 National Electrical Code (NFPA 70-1990). 90°C - XHHW wet or dry locations for ampacity adjustment purposes using NEC section . * All values are nominal and subject to correction. |
Flexible Mineral Insulated Fireproof Power Cable
Fireproof cable
Product Structure
Flexible mineral insulated fireproof cable is made of copper stranded wire, mica tape fire protection layer, mineral mixture, low smoke halogen-free sheath, etc.
Voltage rating (Um=) Flexible mineral insulated fireproof cable
Type |
Product Name |
Voltage rating |
BBTRZ |
Flexible mineral insulated fireproof cable |
Product features
Flexible mineral insulated fireproof cable can maintain normal operation for a while after the fire broke out. It ensures line security and is beneficial for
rescue operation. The cable has passed C、W、Z grade tests required in BS6387 and BS8491 Standard. The tests are 950℃, 180min combustion test, 650℃ water spray test and 950℃ mechanical impact test.
Product structure design
Excellent fire performance--It conforms to BS6387 and BS8491 Standard.
Environmental friendly materials--It’s halogen free, low smoke during combustion.
Flexible structure--There’s no any other similar metal sheath except for
stranded copper wire. Environmental friendly isolation
material is much softer than others. The complete cable
is more flexible and of good fireproof performance.
Easy installation-- The cable can be delivered in coils according to the customer's demand on length. There is no need to use connectors and appropriative terminals. It can be installed in accordance with installation methods for ordinary cables.
Prefabricated branch cable system—We can prefabricate branch joints to meet
the user's need. The system makes
installation more convenient.
Product standard and specification
|
GB/T |
IEC |
DIN VDE |
BS |
Uneven cable insulation and voltage level test |
12706 |
60502 |
|
|
Combustion test and mechanical test |
|
|
|
6027 |
Flame spread test |
60332-3 |
0472 |
|
|
Smoke emission test |
61034-2 |
0472 |
|
|
Circuit integrity test |
60331 |
0472 |
|
|
Halogen content test |
60754-2 |
0472 |
6387 |
|
Combustion test for electrical cable system |
|
|
4102 |
|
Remarks: Rated current-carrying capacity is in accordance with section 523 Cabling system current-carrying capacity, part five Selection and installation of electrical equipment in Building electrical equipment specified in GB/T
Cable installation bending radius: BBTRZ-15D, BBTRZ-2320D
Test standard
Standard for tests in BS6387 and BS8491: Design parameter of flexible mineral insulated fireproof cable is strictly according to BS6387, BS8491, and International Electrotechnical Commission (IEC) Standard. The cable has past specialized tests of the National Fire Administration and Shanghai Electric Cable Research Institute.
DLO,Diesel Locomotive Cable 2KV, EPR/XL-CPE
Rubber Cable
Description
Voltage
2KV
Construction
Sino cables type DLO are manufactured with stranded tinned annealed copper. A paper or polyester tape separates the conductor from the EPDM rubber insulation to aid in stripping. A black, heavy duty CPE sunlight resistant jacket is extruded over the insulation.
Standard
UL44, CSA NO. 38ASTMB3,ICEAS-68-516,NEMA WC-8, or other standards required by customers.
Features
maximum continuous conductor temperature for normal operation is 90°C in dry locations and 75°C for wet.
resists oils, acids, alkalines, heat, flame, and has abrasion resistance.
Applications
Sino cables type DLO is especially suited to supply power to traction motors of diesel-electric locomotives. It is also recommended as a portable cable for drilling rigs, on-shore or off-shore, railroad and transit car wiring, electric earth-moving equipment, in shipyard applications, arc welder supply leads, power and control jumper cable, telcom power supply and motor leads. The cable is suitable for use in wet or dry areas, conduits, ducts, troughs or trays, and where superior electrical properties are desired. suitable for power supply to power appliances, home appliances and movable field electric equipment at 450/750V or less.
Package
Coil, Steel /Wooden Reel ,Wooden Reel or Steel Reel.
Size AWG or MCM |
Stranding |
|
Size AWG or MCM |
Stranding |
|
6 |
63 / 24 |
|
|
650 / 24 |
|
3 |
125 / 24 |
|
|
1100 / 24 |
|
1 / 0 |
275 / 24 |
|
|
1925 / 24 |
|
*cables with smaller . are also available. *All values are nominal and subject
450/750V Factory Price Rubber Cable IEC Standard
Rubber Cable
Description
Voltage
450/750V or less
Construction
1-core: The copper conductor is insulated with natural rubber and sheathed with natural rubber or chloroprene rubber
multi-core: The copper conductor is insulated with natural rubber. Two to six insulated conductors are cabled together with extruded rubber filler, and sheathed with natural rubber or chloroprene rubber.
Standard
IEC 60245, GB/T 5013, or other standards required by customers.
Features
and reliable.
, corrosion, high-Heat and oil Resistant.
Applications
Sino cables type rubber cables are suitable for power supply to power appliances, home appliances and movable field electric equipment at 450/750V or less.
Package
Coil, Steel /Wooden Reel ,Wooden Reel or Steel Reel.
Type |
Description |
Application Range |
YQ |
Natural rubber insulated and natural rubber sheathed light duty flexible cable |
For light movable electric appliances and tools. Type W is suitable for outdoor condition or place where oil exists. |
YQW |
Natural rubber insulated and chloroprene rubber sheathed light duty flexible cable |
|
YZ |
Natural rubber insulated and natural rubber sheathed medium duty flexible cable |
For movable electric appliances and tools. Type W is suitable for outdoor condition or place where oil exists. |
YZW |
Natural rubber insulated and chloroprene rubber sheathed medium duty flexible cable |
|
YC |
Natural rubber insulated and natural rubber sheathed heavy duty flexible cable |
For movable electric appliances, able to bear larger mechanical force .Type W is suitable for outdoor condition or place where oil exists . |
YCW |
Natural rubber insulated and chloroprene rubber sheathed heavy duty flexible cable |
aluminum alloy 1350-H19, 6201-T81,or ACSR conductors insulated Covered Line Wire (ASTM)
Covered Line Wire
Overhead and Underground
Description
Voltage
600V or less
Construction
Sino-cables type covered line wire(ASTM) is manufactured with aluminum alloy 1350-H19, 6201-T81,or ACSR conductors insulated with low density PE, or high density PE or XLPE.
Standard
ASTM B230, B231, B232, B399, B498, or other standards required by customers.
Applications
Sino cables type covered line wire(ASTM) is primarily designed for use on overhead secondary distribution lines. Covered Line Wire is not an electrically insulated conductor and is treated as a bare conductor when installed. The insulation provides protection against circuit interruption due to weather.
Package
coil, steel/wooden reel, wooden reel or steel reel.
Code Word |
Size |
No of Wires |
Insulation Thickness |
Nominal Diameter |
Rated Strength |
Nominal Weight |
Ampacity |
||||
in |
lbs/1000’ |
||||||||||
AWG or Kcmil |
mils |
Bare |
. |
lbs |
Aluminum |
Total |
|||||
LDPE |
HDPE |
XLPE |
A |
||||||||
AAC |
|||||||||||
Plum |
6 |
7 |
30 |
563 |
100 |
||||||
Apricot |
4 |
7 |
30 |
881 |
135 |
||||||
Peach |
2 |
7 |
45 |
1350 |
180 |
||||||
Nectanne |
1 |
7 |
45 |
1740 |
210 |
||||||
Quince |
1/0 |
7 |
60 |
1990 |
240 |
||||||
Haw |
1/0 |
19 |
60 |
2160 |
240 |
||||||
Orange |
2/0 |
7 |
60 |
2510 |
125 |
280 |
|||||
Ironwood |
2/0 |
19 |
60 |
2670 |
125 |
280 |
|||||
Fig |
3/0 |
7 |
60 |
3035 |
157 |
320 |
|||||
Lemon |
3/0 |
19 |
60 |
3310 |
157 |
320 |
|||||
Olive |
4/0 |
7 |
60 |
3810 |
199 |
370 |
|||||
Pomegranate |
4/0 |
19 |
60 |
4020 |
199 |
370 |
Overhead Cable (GB)/ copper, or alloy conductor insulated with PVC, XLPE or PE
Underground
Overhead Cable (GB)
Description
Voltage
Construction
Sino-cables type overhead cable(GB standard) are manufactured with copper, or alloy conductor insulated with PVC, XLPE or PE. Two or three insulated conductors are cabled together.
Single core is also available.
Standard
GB/T 12527, or other standards required by customers.
Features
Max permissible continuous operating temperature of conductor shall not exceed 90°C. Max temperature at short-circuit shall not exceed 250°C.
Applications
Sino cables type overhead cable is suitable for use in overhead transmission and distribution system at .
Package
coil, steel/wooden reel, wooden reel or steel reel.
Type, Description and Application
Type |
Description |
Application |
JKV |
Copper conductor PVC insulated overhead cable |
It is suitable for use in overhead line |
JKLV |
Aluminum conductor PVC insulated overhead cable |
|
JKLHV |
Aluminum alloy conductor PVC insulated overhead cable |
|
JKY |
Copper conductor PE insulated overhead cable |
|
JKLY |
Aluminium conductor PE insulated overhead cable |
|
JKLHY |
Aluminum alloy conductor PE insulated overhead cable |
|
JKYJ |
Copper conductor XLPE insulated overhead cable |
|
JKLYJ |
Aluminum conductor XLPE insulated overhead cable |
|
JKLHYJ |
Aluminum alloy conductor XLPE insulated overhead cable |
|
JKTRY |
Flexible copper conductor PE insulated overhead cable |
|
JKTRYJ |
Flexible copper conductor XLPE insulated overhead cable |
|
JKLYJ/B |
Aluminum conductor natural color XLPE insulated overhead cable |
It is suitable for use in overhead |
JKLHYJ/B |
Aluminum alloy conductor natural color XLPE insulated overhead cable |
|
JKLYJ/Q |
Aluminum conductor light duty thin layer XLPE insulated overhead cable |
|
JKLHYJ/Q |
Aluminum alloy conductor light duty thin layer XLPE insulated overhead cable |
|
JKLY/Q |
Aluminum conductor light duty thin layer PE insulated overhead cable |
|
JKLHY/Q |
Aluminum alloy conductor light duty thin layer PE insulated overhead cable |